The Infona portal uses cookies, i.e. strings of text saved by a browser on the user's device. The portal can access those files and use them to remember the user's data, such as their chosen settings (screen view, interface language, etc.), or their login data. By using the Infona portal the user accepts automatic saving and using this information for portal operation purposes. More information on the subject can be found in the Privacy Policy and Terms of Service. By closing this window the user confirms that they have read the information on cookie usage, and they accept the privacy policy and the way cookies are used by the portal. You can change the cookie settings in your browser.
Real-time hardware-in-the-loop performance assessment of three different passive islanding detection methods for local and wide-area synchrophasor measurements is carried out in this paper. Islanding detection algorithms are deployed within the phasor measurement unit (PMU) using logic equations. Tripping decisions are based on local and wide-area synchrophasors as computed by the PMU, and trips are...
A feature of an Excitation Control System (ECS) for synchronous generators is to enable power system stabilization by providing an additional input to the Automatic Voltage Regulator (AVR) for external stabilization signals. This paper explores this feature by externally generating stabilization signals which are fed as an analog input to a commercial ECS. This allows bypassing the built-in PSS function...
This paper explores the challenges faced during the utilization of synchrophasors received from PMUs in order to estimate the parameters of a DFIG in a real-time. PMUs are installed at the stator and rotor terminals of an 11-KVA DFIG, in order to provide high resolution synchrophasor data at a reporting rate of 50 msgs/sec. These synchrophasors are processed in real-time using an embedded controller...
This paper presents methods and results for experimental performance assessment using Real-Time Hardware-in-the-Loop (RT-HIL) simulation of an Excitation Control System (ECS) for both terminal voltage regulation and power oscillation damping. The ECS configured for this study is Unitrol 1020 from ABB and its performance is assessed for both Automatic Voltage Regulator (Auto) and Field Current Regulator(Manual)modes...
This paper presents the implementation of three different types of Power System Stabilizers (PSS) anda Static Var Compensator with a supplementary Phasor Power Oscillation Damper (POD) control for real-time simulation. The Klein-Rogers-Kundur model is used as test case and the PSS and Phasor-POD's performance is evaluated for both large and small disturbances. Modeling is performed in the MATLAB/Simulink...
This paper presents the implementation of an Open Source SCADA system in a laboratory and discusses methods for PMU data integration into SCADA. SCADA BR is a web-browser based SCADA that enables the user to access monitoring, control and automation equipment over multiple protocols. For implementation, protection relays from SEL are configured as DNP3 outstations to act as slaves and SCADA BR which...
This paper presents the activities carried out in one of the work packages of the Nordic Energy Research funded project Smart Transmission Grid Operation and Control (STRONg2rid). The main objective of the work package is to deploy a state-of-the-art software and hardware for developing power system operation, protection, control and automation applications. Several PMUs have been deployed at partner...
Wide-area synchrophasor applications inherently depend on the underlying IT and communications infrastructure supporting them. In particular, closed loop control systems for power grid oscillation damping is problematic, as it is a complex mixture of power grid monitoring, communication network properties and overall system stability issues. This article offers a holistic analysis of these fields,...
The use of Phasor Measurement Unit (PMU) data in power system operation is of increasing importance. These data are currently used for real-time operation monitoring and off-line analysis. A good understanding of the phasor measurement process is essential for phasor quality analysis as well as for the design of advanced control and protection schemes. In this paper the main computational algorithms...
At the core of the development of “Smart Transmission Grids” is the design, implementation, and testing of synchronized phasor measurement data applications that can supplement Wide-Area Monitoring, Protection, and Control Systems (WAMPAC). Nevertheless, the development of new PMU data-based WAMPAC applications has been relatively slow. The great potential of WAMPAC systems is being limited by this,...
The paper presents a mathematical model of disc-type power transformer winding for frequency response analysis (FRA) based on traveling wave and multiconductor transmission line theories. Each disc of the model is described by traveling wave equations, which are connected to each other in a form of multiconductor transmission line model. The model is applied to FRA simulation in order to study winding...
This paper presents a least square support vector machine (LS-SVM) approach to dissolved gas analysis (DGA) problems for power transformers. Two methods are employed to improve the diagnosis accuracy for DGA analysis. First, bootstrap preprocessing is utilised to equalise the sample numbers for different fault types. Then, the preprocessed samples are inputted to a classier for fault classification...