The Infona portal uses cookies, i.e. strings of text saved by a browser on the user's device. The portal can access those files and use them to remember the user's data, such as their chosen settings (screen view, interface language, etc.), or their login data. By using the Infona portal the user accepts automatic saving and using this information for portal operation purposes. More information on the subject can be found in the Privacy Policy and Terms of Service. By closing this window the user confirms that they have read the information on cookie usage, and they accept the privacy policy and the way cookies are used by the portal. You can change the cookie settings in your browser.
This paper investigates a number of design, operation and lifetime management experiences of transformer protection systems installed on National Grid Electricity Transmission (NGET) networks. The paper will consider the policy, application design and operational experiences under the following categories particularly since the move to numeric protection: Policy and application design Operational...
Power transformers are traditionally protected by differential protection schemes that use voltages and currents to detect abnormalities in the differential zone of protection. For this type of scheme, a short circuit or high magnitude current must be present to initiate a trip. However, this scheme might not be ideal when transformers need to be overloaded to mitigate contingency conditions. Using...
The paper will present implemented protection scheme on two, symmetrical, double core design Phase Shifting Transformers (PST) [6], each rated at 600MVA, 400kV, 866A, 50Hz, ±40° with in total 64 tap positions (32 advance and 32 retard). Thus, every individual tap introduce phase angle shift of 1,25°. The used PST protection scheme follows the protection recommendations published by IEEE [1]. It shall...
Every pump storage hydro power plant has at least three different operating modes of the synchronous machine which can cause possible challenges during the design of the plant protection scheme. These three operating modes are generating mode, pumping mode and machine starting into pumping mode. The main differences between the generating and pumping operating modes are changes in direction of the...