The Infona portal uses cookies, i.e. strings of text saved by a browser on the user's device. The portal can access those files and use them to remember the user's data, such as their chosen settings (screen view, interface language, etc.), or their login data. By using the Infona portal the user accepts automatic saving and using this information for portal operation purposes. More information on the subject can be found in the Privacy Policy and Terms of Service. By closing this window the user confirms that they have read the information on cookie usage, and they accept the privacy policy and the way cookies are used by the portal. You can change the cookie settings in your browser.
This paper presents a combined method for discrimination between inrush current and internal fault current of power transformers. The mentioned method is based on wavelet analysis of power system frequency which is estimated by Prony method. The Prony method is utilized to estimate power system frequency with three consecutive samples rapidly and also Daubechies wavelet family uses the estimated frequency...
This paper presents a new multi-criteria stabilization algorithm of transformer differential protection. Proposed scheme bases on new criteria signals and appropriate operation thresholds. New algorithm employs fuzzy reasoning technique for better discrimination of inrush conditions. The developed stabilization algorithm has been tested with ATP-EMTP generated signals, proving to be reliable and much...
Transformer differential protection schemes normally use multi slope characteristics to provide stability during CT saturation with 2nd harmonic restraint or blocking for inrush conditions. This paper presents new algorithms that have been developed to improve the performance of the differential protection. Extensive testing has been used to demonstrate that the transient bias algorithm can reduce...
This paper reviews the characteristics of inrush current and analyses its causes. The development of digital substation and the concept of integrated protection are also outlined. The paper studies different models to simulate several kinds of inrush and internal short-circuit fault. Through these models, the new composite algorithm is analysed in order to verify the reliability and sensitivity of...