Switching operation of the disconnector in gas-insulated switchgear (GIS) results in very fast transient overvoltage in GIS pipes. In a smart substation, this process induces disturbance voltage on the port of the intelligent component fixed on GIS pipes or placed in the local cabinet nearby, which then may lead to the failure of the equipment. The experimental results of the port disturbance voltage during the switching operation via a 1100 kV test circuit are first reported in this paper. The test arrangement, including both 70 opening operations and 70 closing operations, had been performed. The influences of different grounding schemes of cable shield on port disturbance had been investigated. Three different cases of the terminal load had also been considered: open circuit, short circuit, and 50 Ω. Over 100 000 micro-pulses had been extracted from the disturbance voltage waveforms. The waveform characteristics including peak voltage, rise-time, oscillation frequency, and decaying had been obtained by statistical analysis of these micro-pulses. Furthermore, the differences between measured waveforms and the IEC 61000-4-18 immunity test standard waveform had been discussed.