The procedure developed by the authors simulates an increasing power injection at every bus of the considered sample and checks the violation of operating limits (current, SVV, RVC) in order to determine the maximum admissible nodal injection. The procedure is applied to a huge network data set, corresponding to real Italian MV grids and representing a significant subset (7%) of the system.