This work discusses about the pressure drop and heat transfer characteristics of a plain fin, a strip fin and combinations thereof in the fin-and-tube heat exchanger. Experimental apparatus and test algorithm using scale-up model fin geometry are discussed. The present work uses the electric heaters inside of the tube as the heating source to simulate the hot water loop in the wind tunnel test. The test results of the plain and strip fins are compared with the existing correlation and experimental data. It was found that a hybrid fin, plain fin at front row and strip fin at rear row, was more effective to enhance the heat transfer than that of the whole strip fin at the same fan power.Dans l'article, on traite des caracteristiques de la chute de pression et du transfert de chaleur d'une ailette lisse, d'une ailette gaufree et de combinaisons de ces deux types d'ailettes dans un echangeur de chaleur a tubes ailetes. Le dispositif experimental et l'algorithme utilisant une geometrie des ailettes echelonnees sont presentes. On utilise des equipements de chauffage electriques a l'interieur du tube, comme source de chaleur, pour simuler la boucle d'eau chaude dans le tunnel experimental. Les resultats experimentaux concernant les ailettes lisses et les ailettes gaufrees sont compares avec la correlation existante et les donnees experimentales. On a observe que des ailettes hybrides, c'est-a-dire lisses a la rangee frontale et gaufrees a la rangee arriere, etaient plus efficaces pour intensifier le transfert de chaleur que des ailettes entierement gaufrees, a la meme puissance du ventilateur.