The Infona portal uses cookies, i.e. strings of text saved by a browser on the user's device. The portal can access those files and use them to remember the user's data, such as their chosen settings (screen view, interface language, etc.), or their login data. By using the Infona portal the user accepts automatic saving and using this information for portal operation purposes. More information on the subject can be found in the Privacy Policy and Terms of Service. By closing this window the user confirms that they have read the information on cookie usage, and they accept the privacy policy and the way cookies are used by the portal. You can change the cookie settings in your browser.
In this paper, a control strategy for the parallel operation of three-phase inverters in a modular online uninterruptable power supply (UPS) system is proposed. The UPS system is composed of a number of dc/acs with LC filter connected to the same ac critical bus and an ac/dc that forms the dc bus. The proposed control includes two layers: 1) individual layer and 2) recovery layer. In individual layer,...
In a modular uninterruptible power supplies (UPS), each DC/AC module was designed to work in a circular way considering the reliability and power stress issues of the whole system. Thus unsynchronized PWMs will occur if any of the DC/AC modules is plugged in or out of the system at any time. On the other hand, modular difference is another issue that will bring such kind of circulating current. In...
In this paper, a simplified control architecture, including individual layer control and recover layer control, is proposed for a modular online uninterruptible power supply (UPS) system is presented. The parallel control algorithm of for the DC/AC modules are mainly concentrates on the active power sharing performance due to the existence of the shunt active power filter (APF). APF will deal with...
In this paper a control strategy for the parallel operation of three-phase inverters in a modular online uninterruptable power supply (UPS) system is proposed. The UPS system is composed of a number for DC/ACs with LC filter connected to the same AC critical bus and an AC/DC that forms the DC bus. The proposed control is designated in two layers, individual layer and recovery layer. In individual...