The Infona portal uses cookies, i.e. strings of text saved by a browser on the user's device. The portal can access those files and use them to remember the user's data, such as their chosen settings (screen view, interface language, etc.), or their login data. By using the Infona portal the user accepts automatic saving and using this information for portal operation purposes. More information on the subject can be found in the Privacy Policy and Terms of Service. By closing this window the user confirms that they have read the information on cookie usage, and they accept the privacy policy and the way cookies are used by the portal. You can change the cookie settings in your browser.
A stator earth fault protection scheme based on fault current is presented in this paper. It trips out the faulted generator only if the fault current following the breakdown channel exceeds the tolerance capacity of the generator. Otherwise, it will just emit alarm signals. This protection scheme can avoid unnecessary trip-out of large generator, which influences the safe operation of power system,...
This paper presents a stator ground protection scheme based on the fault current flowing in the breakdown channel. It trips only if the fault current exceeds the fault current tolerance capacity of the generator. Otherwise, it will just emit alarm signals. Thereby, the unnecessary trip-out of large generator can be avoided. The stability of the power system and the generator security can then be ensured...
As affected by electromagnetic coupling, the sequence impedance of parallel multi-circuit cable lines is different from that of single-circuit ones. Based on “conductor-ground” loop, derived from the matrix form of voltage equations, a new algorithm of parameters calculation for multi-circuit cable lines is presented. To consider the influence of metal sheath, the algorithm treats it the same as core...
Closing a transformer without load will lead to the emergence of sympathetic inrush current in adjacent transformer. Sympathetic inrush current always causes mal-operation of protective relay and harmonic over-voltage. Based on simplified equivalent circuit of two shunt-wound transformers, the magnetic analytical expression and rule of bias magnet attenuation are analyzed. After that, the reasons...
Because of the complexity of topology and control strategy, the mid-voltage and large power frequency converter has more failure types and fault feature relatively. Then the correct identification and isolation of its internal faults are very important. Based on the MATLAB/Simulink, this paper established a complete fault simulation model of IGCT series mid-voltage & mid-power three level frequency...