The Infona portal uses cookies, i.e. strings of text saved by a browser on the user's device. The portal can access those files and use them to remember the user's data, such as their chosen settings (screen view, interface language, etc.), or their login data. By using the Infona portal the user accepts automatic saving and using this information for portal operation purposes. More information on the subject can be found in the Privacy Policy and Terms of Service. By closing this window the user confirms that they have read the information on cookie usage, and they accept the privacy policy and the way cookies are used by the portal. You can change the cookie settings in your browser.
Further to a previous experimental study on the heat exchanger circuitry number for a two-way discharge active chilled beam terminal unit, an investigation of the tube connecting sequences is conducted in this paper. Given a typical air side operating condition, in situ air velocity profile across the heat exchanger is measured and non-uniformities of the air flow caused by the entrainment effect...
This paper presents a performance comparison study of heat exchangers with different circuitry arrangements for active chilled beam (ACB) applications. Supported by a two-way discharge ACB terminal unit and a performance test pilot plant, four 2-rows plain fin and tube heat exchangers, namely, 1-circuit, 2-circuits, 4-circuits, and 8-circuits, are investigated under a wide range of chilled water volume...