The Infona portal uses cookies, i.e. strings of text saved by a browser on the user's device. The portal can access those files and use them to remember the user's data, such as their chosen settings (screen view, interface language, etc.), or their login data. By using the Infona portal the user accepts automatic saving and using this information for portal operation purposes. More information on the subject can be found in the Privacy Policy and Terms of Service. By closing this window the user confirms that they have read the information on cookie usage, and they accept the privacy policy and the way cookies are used by the portal. You can change the cookie settings in your browser.
In this paper, a chirp detector of the current waveforms is evaluated for locating the earth faults in unearthed MV networks where it is used to precisely localize the travelling wave arrival times created by the fault occurrence. Chirp modulation, or linear frequency modulation employs sinusoidal waveforms whose instantaneous frequency increases or decreases linearly over time. These waveforms are...
In a Bayesian selectivity technique has been introduced to identify the faulty feeder in compensated medium voltage (MV) networks. The proposed technique has been based on a conditional probabilistic method applied on transient features extracted from the residual currents only using the Discrete Wavelet Transform (DWT). In this paper, the performance of this selectivity technique is evaluated when...
In this paper, a Bayesian selectivity technique is introduced to identify the faulty feeder in compensated medium voltage (MV) networks. The proposed technique is based on a conditional probabilistic method applied on features extracted from the residual currents only using the discrete wavelet transform (DWT). DWT enhances to localize initial transients generated in the network due to the fault event...
In this paper, the windowed standard deviation (WSTD) is used to extract the initial transients created in residual current waveforms generated due to earth faults in medium voltage (MV) compensated networks. The sliding window width used for computing the standard deviation is evaluated from the frequency filter point of view. The fault cases occurring in a compensated 20 kV network are simulated...