The Infona portal uses cookies, i.e. strings of text saved by a browser on the user's device. The portal can access those files and use them to remember the user's data, such as their chosen settings (screen view, interface language, etc.), or their login data. By using the Infona portal the user accepts automatic saving and using this information for portal operation purposes. More information on the subject can be found in the Privacy Policy and Terms of Service. By closing this window the user confirms that they have read the information on cookie usage, and they accept the privacy policy and the way cookies are used by the portal. You can change the cookie settings in your browser.
The paper investigates the pulsed AMF arc control on the vacuum arc and the post arc characteristic to reveal the mechanism of AMF arc control in different control time and find the proper AMF arc control. The pulsed AMF control system is designed and the pulse width is adjusting from 1.5ms to 10ms. The test circuit is set up in the synthetic test and the test VI is transparency in order to observe...
This paper proposes the equivalent circuit of dynamic VD (PVD) in multi-break vacuum circuit breakers (VCBs). The equivalent circuit is composed of controlled post-arc sources, post arc resistors and equivalent capacitors. The PVD is divided into four processes: the initial transient recovery voltage (TRV) process, the oscillating TRV process, the stable TRV process and the power-frequency voltage...
The current interruption capacity of gas gap can be enhanced by series connecting with vacuum gap in hybrid circuit breaker. For the purpose of compensating the inferior interruption performance of CO2 gas gap, as the substitute for SF6 gas gap, the interruption principle and the dielectric strength recovery process of the series gaps of vacuum gap and CO2 gas gap are studied in this paper. Based...
CO2 gas is a possible substitute for SF6 gas in circuit breaker with relatively superior arc interruption performance. To enhance the interruption capacity of the circuit breaker which employs CO2 gas as its arc interruption dielectric, the interruption principle of the hybrid circuit breaker composed of vacuum interrupter and CO2 gas interrupter is studied. Based on the black-box arc models of hybrid...
The paper established the simulation model of series vacuum arc of Vacuum Circuit Breaker (VCB) with double-break using Magneto Hydro Dynamic (MHD) model. To gain the matching characteristics of series vacuum arc, the influence of series different vacuum gaps and interactional magnetic field was analyzed. The distribution of micro-characteristics was depended on the axial magnetic field causing by...
For the purpose of repetitive pulsed power applications, specially designed TVSs were tested under different high frequency currents in this contribution. Two TVSs named TVS-1 and TVS-2 respectively were designed to investigate the high frequency current breaking characteristics with or without an axial magnetic field (AMF) aid. The TVS with AMF at the cup-like anode can generate a magnetic field...